[su_tabs vertical=”yes”][su_tab title=”Product Details”]
Product Details
| Function | Range | Resolution | Measuring range | Accuracy |
| Earth resistance Re (Rg at ρ measurement) | 2Ω | 0.001Ω | 0.03 – 2.099Ω | ±2%rdg±0.03Ω |
| 20Ω | 0.01Ω | 0.03 – 20.99Ω | ±2%rdg±5dgt (*1) | |
| 200Ω | 0.1Ω | 0.3 – 209.9Ω | ||
| 2000Ω | 1Ω | 3 – 2099Ω | ||
| 20kΩ | 10Ω | 0.03k – 20.99kΩ | ||
| 200kΩ | 100Ω | 0.3k – 209.9kΩ | ||
| Auxiliary earth resistance Rh, Rs | 8% of Re+Rh+Rs | |||
| Earth resistivity ρ | 2Ω | 0.1Ω·mm – 1Ω·m Autoranging | 0.2 – 395.6Ω·m | ρ=2×π×a×Rg (*2) |
| 20Ω | 0.2 – 3956Ω·m | |||
| 200Ω | 20 – 39.56kΩ·m | |||
| 2000Ω | 0.2 – 395.6kΩ·m | |||
| 20kΩ | 2.0 – 1999kΩ·m | |||
| 200kΩ | ||||
| Series interference voltage Ust (A.C only) (*3) | 50V | 0.1V | 0 – 50.9Vrms | ±2%rdg±2dgt (50/60Hz) |
| ±3%rdg±2dgt (40 – 500Hz) | ||||
| Frequency Fst | Autoranging | 0.1Hz 1Hz | 40Hz – 500Hz | ±1%rdg±2dgt |
| Measuring method | Earth resistance: Fall-of-potential method (currents and voltages measured via the Probes) Measurement method of Earth Resistivity (ρ): Wenner 4-pole method Series interference voltage (earth voltage) RMS Rectifier (between the E-S Terminals) | |||
| Memory capacity | 800 data | |||
| Communication Interface | Model 8212-USB Optical Adaptor | |||
| LCD | Dot-matrix 192×64 monochrome | |||
| Over-range Indication | “OL” | |||
| Overload Protection | between E-S(P) and between E-H(C) terminals AC280V / 10 sec. | |||
| Applicable standards | IEC 61010-1 CAT III 300V, CAT IV 150V Pollution degree 2 IEC 61010-031, IEC 61557-1, 5, IEC 61326-1 (EMC), IEC 60529 (IP54) | |||
| Power source | DC12V : sizeAA manganese dry battery (R6) × 8 (Auto power off: approx. 5 minutes) | |||
| Dimensions | 167(L) × 185(W) × 89(D) mm | |||
| Weight | approx. 900g (including batteries) | |||
| Accessories | 7229A (Earth precision measurement), 7238A (Simplified measurement test leads), 8032 (Auxiliary earth spikes [2 spiks/set])×2 sets (4 spikes in total), 8200-04 (Cord reel [4 pcs])×1 set, 8212-USB (USB adaptor with “KEW Report(Software)”), 9121 (Shoulder strap), 9125 (Carrying case), R6 × 8, Instruction manual, Calibration certificate | |||
| Optional | 8212-RS232C (RS232C adaptor with “KEW Report(Software)”) | |||
[/su_tab]
[/su_tabs]