UT595 Multifunction Installation Tester - Variety House

UT595 Multifunction Installation Tester

155,250

UT595 multifunction testers mainly test RCD, loop/line impedance, earth resistance continuity, insulation resistance and AC/DC voltage. They are applicable to electrical installation, inspection and repair at home or in construction industry.

 

155,250

Buy Now
Add to cart
68 / 100

Features

● 9999-count LCD display with analogue bar

● 250V~1000V DC insulation resistance test
● 200mA earth-resistance continuity test
● Loop impedance/Prospective Fault Current (PFC)/Prospective Short Current (PSC) test
● Lock test
● RCD trip time test and the data storage with one key
● Full/Half wave and count downing (30s) test mode selectable
● 0°/180° phase angle option to detect the fastest trigger time
● Trip current test of RCD trip time X2
● RCD trip trigger current test
● Phase sequence and missing test
● AC/DC voltage auto check and test
● Connection check with status real-time display
● White backlight; auto power off

Specifications

68 / 100

Specifications

SpecificationsRangeUT593UT595
Insulation resistance (Ω)Output voltage250V/500V/1000V±10%
250V0.05MΩ~250MΩ±(5%+5)
500V0.05MΩ~500MΩ
1000V0.05MΩ~1000MΩ
Short-circuit current<2mA
Low-resistance continuity testRange0.00Ω~199Ω±(2%+5)
Test current0.00~2Ω: >200mA
Line impedance (Ω)Range0.01Ω~2000Ω±(5%+5)
Operating voltage (Frequency)230V (45Hz~65Hz)
Test current20A
PFC test0kA~26kA
Loop impedance (Ω)Range0.01Ω~2000Ω±(5%+5)
Operating voltage (Frequency)195V~253V (45Hz~65Hz)
Test current20A
PFC test0kA~26kA
Non-trip loop impedance (Ω)Range1.00Ω~2000Ω±(5%+5)
Operating voltage (Frequency)195V~253V (45Hz~65Hz)
Test current15mA
PFC test0kA~26kA
RCD testOperating voltage (Frequency)195V~253V (45Hz~65Hz)
Test current10mA/30mA/100mA/300mA/500mA±10%
Trip time×1/2 *I△n  Range: 0ms~2000ms±(5%+5)
×1 *I△n  Range: 0ms~300ms
×1 *I△n  Range: 0ms~500ms (Select count down)
×2 *I△n  Range: 0ms~150ms±(5%+5)
×2 *I△n  Range: 0ms~200ms (Select count down)±(5%+5)
×5 *I△n  Range: 0ms~40ms±(5%+5)
Phase sequence testOperating voltage (Frequency)100V~440V  (45Hz~65Hz)
DisplayPhase sequence: L1→ L2→ L3, forward rotation; L1→ L3→ L2 reverse rotation
Ramp RCD testTest current10mA/30mA/100mA/300mA/500mA±10%
AC voltage (V)Range0V~440V±(5%+2)
Frequency response45Hz~60Hz
Resolution1V
Features
Display count9999
Auto power off
Low battery indication
Data storage
LCD backlight
Auto half-wave test
RCD count down test30s
RCD half-wave test
Phase conversion (RCD)0° and 180°

General Characteristics

68 / 100

General Characteristics

Power1.5V battery (5#) × 6
LCD size125mm × 37mm
Product colorRed and grey
Product net weight1000g
Product size210mm × 175mm × 90 mm
Standard accessoriesBattery, test leads (red×1, green×1, black×1), special power test lead, remote-control test lead
Standard individual packingGift box, manual, tool box
Standard quantity per carton4pcs
Standard carton measurement510mm×330mm×300mm
Standard carton gross weight15kg
Back to top